Pad mounted transformer YB27-40.5/YB27-12

YB27 prefabricated substation is a domestic American-style box transformer launched by Huanghua Group. As an important power supply unit in the cable distribution network, this product is a complete set of prefabricated products integrating high-voltage control, protection, substation, and distribution equipment, and is widely used in urban and rural distribution networks.

This product places high-voltage load switches and high-voltage fuses in the transformer oil, and has two structural forms: sharing the box with the transformer body or separating the box. The oil tank adopts a fully sealed structure and is equipped with an oil temperature gauge, oil level gauge, and pressure gauge. Components such as pressure relief valves and oil drain valves are used to monitor the operating status of the transformer. This product is divided into ring network type, terminal type, and dual power supply type. In order to make this product more suitable for the actual requirements of my country's power grid, the group company has also launched plug-in dry fuses, and the melting of the fuse does not affect the performance of the transformer oil. According to the complexity of the low-voltage feed-out requirements, Huanghua Group's YB27 products are divided into three shell forms: standard reinforced type and comprehensive type, so that users and design units can be more flexible and economical when selecting.


  • Usage environment

    △ Ambient temperature: Maximum temperature +40℃, minimum temperature -30°C;

    △ Altitude: < 1000m;

    △ Wind speed: not more than 34m/s (not more than 700Pa);

    △ Humidity: Daily average relative humidity is not more than 95%; Monthly relative humidity is not more than 90%; When ordering this product beyond the above conditions, you can negotiate with our company.

    △ Shockproof: Horizontal acceleration is not more than 0.4m/s2, vertical acceleration is not more than 0.15m/s2;

    △ Installation site inclination: not more than 3°:

    △ Installation environment: The surrounding air is not obviously polluted by corrosive and flammable gases, and there is no severe vibration at the installation site;


  • Model and meaning

    图片5.png

Technical Parameter


Performance level of S9, S10, S11 series oil-immersed transformers for 10kV prefabricated substations


 

No.

 

Rated capacity

kVA)

Rated voltage

 

Voltage TAPS%)

 

Vector Group

 

No-load current%)

LossesW)

 

Impendance Voltage      

%)

 

Noise

dB)

 

 

Temperature rise

 

H.V.kV)

 

L.V.kV)

No load

Load

S10/S11

S13

S10

S11

S13

S13

S10/ S11

1

30

 

 

 

 

 

 

 

 

 

6

 

6.3

 

10

 

 

 

 

 

 

 

 

 

0.4

 

 

 

 

0.69)

 

 

 

 

 

 

 

 

 

±5

 

 

 

 

±2×2.5)

 

 

 

 

 

 

 

 

 

Yyn0

 

 

 

 

Dyn11

2.0

1.2

130


80

600

 

 

 

 

 

 

 

 

4

 

 

 

 

 

 

 

 

 

 

 

5.5

 

 

 

 

 

Top oil temperature 60Coil 65

2

50

1.8

1.0

170


100

870

3

63

1.5

0.95

200


110

1040

4

80

1.2

0.95

250


130

1250

5

100

1.1

0.90

290


150

1500

6

125

1.0

0.90

270

170

1800

7

160

1.0

0.80

310

200

2200

8

200

0.8

0.80

375

240

2600

9

250

0.8

0.70

455

400

290

3050

3000

10

315

0.7

0.70

540

470

340

3650

3600

11

400

0.7

0.65

650

570

410

4300

4200

12

500

0.6

0.65

775

680

480

5100

5000

13

630

0.6

0.45

920

800

570

6200

6000

 

 

 

4.5

14

800

0.6

0.45

1120

980

700

7500

7400

15

1000

0.5

0.45

1320

1150

830

10300

9860

16

1250

0.5

0.40

1560

1360

970

12800

12000

17

1600

0.5

0.40

1880

1640

1170

14500

14000

Note: a. According to customer requirements, the high voltage tapping range of the transformer can be designed to be ±2 × 2.5%.

b. According to customer requirements, the low voltage of the transformer can be designed to be 0.69kV.

Load switch performance parameters

 

Rated currentA)

 

Rated voltageV)

 

Impact pressure resistancekV)

Power frequency withstand voltage1min.kV)

Rated short-time withstand currentkA/s)

 

 

Short circuit closing currentkA)

Short circuit peak withstand currentkA)

Load operation times

Number of mechanical operations

315

12

75

42

12.5/2

31.5

31.5

100

2000

630

12

75

42

16/4

40

40

100

3000

 


Structural characteristics

Compact structure and small size, only about 1/5~1/3 of the European box transformer with the same capacity, greatly reducing the floor space.

Fully sealed and fully insulated structure, no insulation distance required, reliable protection of personal safety.

High-voltage wiring can be used for both ring network and terminal, flexible power supply mode and high reliability.

Transformer has excellent performance: low loss, low noise, low temperature rise; strong overload capacity, short circuit resistance, strong impact resistance.

Meet various low-voltage feed requirements, can be selected according to the scheme, or can be designed by yourself;

The cable head has two types: 200A elbow plug and 600A "T" type fixed cable connector, both of which can be equipped with fully insulated zinc oxide arrester. The 200A cable head can be plugged and unplugged with load, and can also play the role of isolating switch.


Structural diagram

image.png

Configuration diagram

Scan QR code
Follow Huanghua Group

Contact Us

wm@huanghua.com cc@huanghua.com