HKB9F-100+ZF fee-controlled energy meter external circuit breaker uses a small circuit breaker with short-circuit overload protection as the main switch, and is equipped with an ultra-small intelligent electric operator with a microprocessor. It automatically controls the opening or closing of the circuit breaker by detecting the electric and air control signal. It is used in conjunction with the prepaid electricity meter to realize the automatic control of opening for arrears and closing for payment.

 

It complies with the "Technical Specifications for External Circuit Breakers of Energy Meters" of the State Grid Corporation of China and the China Southern Power Grid and "GB/T10963.1 Overcurrent Protection Circuit Breakers for Household and Similar Places Part 1: Circuit Breakers for AC".


  • Usage environment

    △ Altitude: ≤2000m

    △ Installation category: Ⅱ, Ⅲ

    △ Installation method: Embedded vertical DIN standard rail installation

    △ Pollution level: 2



  • Model and meaning

    图片18.png

Technical Parameter

Frame grade

63

Rated insulation voltage

500

Rated impulse withstand voltage

6kV

Rated frequency

50Hz

Number of poles

2P, 3P

Instantaneous tripping type

C

Rated short-circuit capacity

6kA(80-100A),10kA(10-63A)

Operating short-circuit capacity

6kA(80-100A),7.5kA(10-63A)

Mechanical life

10000

Electrical life

6000

Working range

(65%~120%)Un

Control signal voltage

AC220V 50Hz

Power-on delay time

State Grid 4St5S Southern Grid 7St8S

Automatic closing time

t3S

Working temperature

-40~+70

Relative humidity

+20not higher than 95%;+40not higher than 50%

Signal connection wire cross-sectional area

0.3mm²

Signal connection wire length

300mm (other lengths available)

Grid distance

50mm

Compliance with standards

IEC60898-1,GB/T 0963.1

Certification

CCC/CB

Overcurrent protection characteristics

No.

Rated current of release (A)

Initial Status

Test current

Schedule

Expected Results

Remark

1

10-100

Cold

1.13ln

t≤1h(≤63A)

t≤2h(≥80A)

No tripping


2

10-100

Immediately after the previous test

1.45In

t<1h(≤63A)

t<2h(≥80A)

Tripping

The current rises steadily to the specified value within 5s.

3

In≤32

Cold

2.55ln

1s <t< 60s

Tripping


In32

Cold

2.55In

1s <t< 120s

Tripping


4

1-100

Cold

5ln

t≤ 0.1s

No tripping

Type C

10ln

t< 0.1s

Tripping

图片20.png

Structural characteristics
Structural diagram

图片21.png

Configuration diagram

Scan QR code
Follow Huanghua Group

Contact Us