HMDS Low-voltage Switchgear Panel, Fixed Divider Type

HMDS low-voltage fixed separation switchgear has internationally advanced interval combined low-voltage complete switchgear, which consists of two parts: power distribution center (PC) and motor control center (MCC). It is used in three-phase distribution systems with AC 50Hz and rated working voltage of 660V and below. It is used for power receiving, feeding, lighting, motor control and reactive power compensation in power plants, substations, industrial and mining enterprises and high-rise buildings.

With the continuous advancement of my country's industrialization process, low-voltage complete switchgear has been widely used. At present, domestic low-voltage complete switchgear has formed different types of low-voltage cabinets, such as fixed, drawer, and fixed interval, which can meet the needs of different users. Due to the wear of connectors and busbars during use, the drawer-type switchgear is prone to poor contact and busbar heating. Various types of drawer push mechanisms and interlocking mechanisms are frequently operated and easily damaged and broken. The overall weight of the high-current drawer cabinet and the strength of the plug-in are large, which affects the advancement and pulling out of the drawer. The heat dissipation of the vertical channel of the drawer cabinet is relatively poor. The vertical busbar current carrying capacity of the standard drawer cabinet is basically around the rated current of 1000~1250A, which is not conducive to the production of large current in the feeder circuit. When the feeder circuit is electrically operated, an interlocking device needs to be added to make the drawer, which reduces the safety. In order to overcome the various defects of the drawer-type switchgear, a fixed interval switchgear has been developed.



  • Usage environment

    The ambient air temperature shall not be higher than +40or lower than -5, and the average temperature within 24 hours shall not be higher than +35. If it exceeds, it shall be operated at reduced capacity according to the actual situation.

    For indoor use, the altitude of the place of use shall not exceed 2000m.

    The relative humidity of the ambient air shall not exceed 50% when the maximum temperature is +40°C, and a higher relative humidity is allowed at lower temperatures: such as 90% at +20. The influence of condensation may occur occasionally due to temperature changes should be considered.

    When the device is installed, the inclination with the vertical plane shall not exceed 5%, and the whole set of cabinets shall be relatively flat. The device should be installed in a place without severe vibration and impact and where the electrical components are not corroded inappropriately.

    If the user has special requirements, they can negotiate with the manufacturer to solve them.


  • Model and meaning

    图片3.png

Technical Parameter

Items

Technical parameters

Rated voltage

Rated insulation voltage

AC 660V


Rated working voltage

AC 380V


Rated pulse withstand voltage

AC 2500v

Rated Frequency

50 Hz

Rated current of main busbar(A)

Maximum working current of main busbar

Up to 5000A

Operating power

Rated voltage

AC 220V

Cabinet external dimensions

Height x Width x Depth

2200×1000(800/600)×1000(80)